Electrical calculations, worked through

Voltage drop, conductor sizing, conduit and box fill, load, power factor and DC circuits. Every tool shows the formula, the code reference and the working behind the answer.

Built for people who have to justify the number

An electrical calculation is rarely just for you. It goes on a permit application, into a load schedule, or in front of an inspector. That is why every tool on AmpCalcs states the formula it used, names the code article it follows, and shows the intermediate values instead of only the final answer.

Start from what you have, not from the tool you want

Most people arrive here with one of these, and the tool you need follows from it. Pick the row that matches what is in front of you; the rest of this page is the rules that apply once you have picked.

Five rules that decide most of these answers

Each tool on this site applies the same handful of rules. They are worth knowing because they are the reason two people with the same numbers can get different answers, and they are the reason a figure that looks generous is sometimes not.

Three worked examples

1. One load, two distances

A 240 V single-phase circuit carries a 40 A continuous load over copper, 60 ft one way. The design current is 40 × 1.25 = 50 A, so the conductor has to carry 50 A. From the 75 degree column, 8 AWG at 50 A qualifies and is not one of the small conductors with a ceiling under 240.4(D). Its voltage drop over 60 ft is about 4.69 V, or 1.95 percent, comfortably inside the 3 percent used for a branch circuit.

Now double the distance to 120 ft and change nothing else. The ampacity answer stays 8 AWG because ampacity does not know how long the run is. The drop answer does not stay: 8 AWG over 120 ft gives about 9.38 V, or 3.91 percent, which is outside the 3 percent target. 6 AWG brings it to about 5.90 V, or 2.46 percent, and that is the size you install. Nothing about the load changed; only the distance did.

2. Five conductors into a raceway

Four 8 AWG THHN conductors plus one equipment grounding conductor is five conductors, so the 40 percent limit applies. From Chapter 9 Table 5, one 8 AWG THHN conductor is 0.0366 square inches, so the five of them occupy 0.1830 square inches. A 3/4 inch EMT has 0.533 square inches of internal area from Table 4, which puts the fill at 34.3 percent and passes. That same raceway holds at most five 8 AWG conductors. A 1 inch EMT has 0.864 square inches, drops the fill to 21.2 percent, and holds up to nine.

The trade size you pick changes the answer, which is why a raceway specified before the conductor count was final is often the reason the pull does not fit.

3. A box with room left in it

Take a 4 inch square metal box, 2-1/8 inches deep, 30.3 cubic inches. With 12 AWG as the largest conductor, each allowance is 2.25 cubic inches. Three current-carrying conductors, one grounding conductor and one device yoke count as six allowances: three for the conductors, one for all the grounds together, and two for the yoke. Six allowances is 13.50 cubic inches, so 16.80 cubic inches are still free.

Six current-carrying conductors in the same box count as nine allowances, or 20.25 cubic inches, which still passes. The point of the calculation is not that this box is full; it is that the free space you can see is not the free space the code counts, and the box that looks tightest is often the one with room.

What these calculators do not decide

Each tool here answers one arithmetic question and stops there. Five things sit outside that arithmetic and each of them can change the answer, so none of these numbers is a design on its own.

What is here

Instruments for the checks these calculators hand you

Every number on this site comes out of a table, a formula or a code article. Four things turn that number into something you can act on: measuring what is actually there, bending the raceway it has to fit in, identifying it once it is live, and reading the table on site.

  • Digital clamp meter — The nameplate on a panel tells you what a circuit was rated for, not what it draws now. A clamp meter reads the running current on each leg without opening the circuit, which is how you find the load that is actually on before you size anything to it.
  • Hand conduit bender — The raceway has to be bent to reach the box, and the bend is made on site from the length you chose. A hand bender puts the offset where the drawing needs it and keeps the wall of the EMT from flattening on the way.
  • Panel label maker — A service, feeder or branch circuit has to be identified at its disconnecting means so the next person can tell what they are opening. A label printer puts that identification on every circuit instead of on one you remembered.
  • Ampacity chart card — The 60, 75 and 90 degree columns of the ampacity table and the small-conductor ceilings are easier to read off a card in a crawl space than off a phone screen, and the card stays in your pocket when the phone has no signal.

As an Amazon Associate I earn from qualifying purchases. The links above are affiliate links — if you buy through one, the price you pay is unchanged and a small commission helps keep these calculators free. Items are listed because the job calls for them, not because of commission rates.

Where these numbers come from

Ampacity values are read from the copper column of NEC Table 310.16, kept separate per temperature rating rather than merged. Conductor areas follow Chapter 9 Table 5 for THHN, raceway areas Table 4 for EMT, and K is 12.9 ohm-circular-mil per foot for copper at 75 degrees. The safety rules the arithmetic sits inside are federal requirements, and the ampere itself is an SI unit with a fixed definition.

  • 29 CFR 1910 Subpart S — Electrical (eCFR) — 1910.303 general requirements, 1910.304 wiring design and protection including overcurrent protection and grounding of terminals and devices, 1910.308 special systems including marking of disconnecting means, and 1910.331 to 1910.360 safety-related work practices for qualified persons.
  • OSHA — Electrical — the standards that apply to people exposed to electrical hazards, described as protecting employees against electric shock, electrocution, fires and explosions.
  • NFPA 70, National Electrical Code — the code the ampacity, overcurrent and fill rules above come from, and the process by which it is revised.
  • NIST — SI Units, Electric Current — the ampere, defined from the fixed numerical value of the elementary charge, which is why current is the unit every calculation here starts and ends in.
  • Ampacity — the maximum current that can be applied continuously without harming a device or system, as the National Electrical Code defines it.
  • Voltage drop — the loss of electric potential along the path of a current, across conductors, contacts and connectors, and the reason it is dissipated as heat.

Everything runs in your browser. Nothing is uploaded, there is no account, and the calculators keep working offline once the page has loaded.

FAQ

Which electrical calculator should I start with?

Start from the information you actually have. A nameplate in kVA or kW goes to the kVA calculator first; a load in amps plus a run length goes straight to the wire size calculator; conductors already chosen go to the conduit fill calculator; and a bundle of conductors going into an outlet box goes to the box fill calculator.

Why does a continuous load get multiplied by 1.25?

A continuous load is one expected to run for three hours or more. NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders require the conductor to be sized at 125 percent of the load current, and the overcurrent device carries the same factor. A 16 A continuous load is therefore designed as 20 A.

Should I use the 60, 75 or 90 degree column of the ampacity table?

Use the column set by the weakest component in the circuit, which is usually the termination rather than the conductor. Most breakers and lugs are rated 75 degrees, so a 90 degree conductor landed on one of them may only be used at its 75 degree ampacity.

What voltage drop is acceptable?

Three percent is the figure used for a branch circuit and five percent for the combined feeder and branch circuit. Voltage drop is a separate check from ampacity, and on a long run it is often the one that decides the conductor size.

Why does the answer change when I choose a different conduit size?

Conduit fill is a percentage of the raceway internal area, and that area comes from NEC Chapter 9 Table 4 for the raceway and Table 5 for the conductor insulation. A larger raceway lowers the percentage and raises the number of conductors that fit.

How is an outlet box counted?

NEC 314.16(B): each current-carrying conductor takes one allowance, all the equipment grounding conductors together take one allowance, each device yoke takes two, and an internal cable clamp takes one. The allowance is the volume of the largest conductor present.

Does power factor change how a circuit is sized?

It changes the current. Real power in kW divided by power factor gives the kVA the equipment actually has to carry, and the kVA is what sets the conductor size. Lowering power factor on an unchanged load raises the current and can change the answer.

Can these calculators be used for an actual installation?

They give the arithmetic, under the assumptions stated on each page: 30 degrees C ambient, no more than three current-carrying conductors in a raceway, and the conductor distances as entered. Ambient correction, conductor bundling and termination ratings have to be applied on top, and the result still has to be installed to the current code and inspected.

More electrical tools

Have a suggestion?

Missing a feature or found something off? Tell us — user suggestions decide what we build next.