Built for people who have to justify the number
An electrical calculation is rarely just for you. It goes on a permit application, into a load schedule, or in front of an inspector. That is why every tool on AmpCalcs states the formula it used, names the code article it follows, and shows the intermediate values instead of only the final answer.
Start from what you have, not from the tool you want
Most people arrive here with one of these, and the tool you need follows from it. Pick the row that matches what is in front of you; the rest of this page is the rules that apply once you have picked.
- A nameplate in kVA or kW. Start at the kVA calculator to turn it into amps, then move to the wire size calculator. The square root of three is the step people skip and the one that makes a 480 V answer come out 1.7 times too low.
- A load in amps and a run length in feet. Go straight to the wire size calculator. It checks ampacity and voltage drop together, because the larger of the two answers wins and the smaller one is the one you would have forgotten.
- A reading at the far end that is lower than it should be. Use the voltage drop calculator on its own. Nothing about a circuit changes the measurement; what changes is whether the conductor is long enough for the current it is carrying.
- Conductor already chosen and a raceway to check. The conduit fill calculator answers it directly: the percentage of the raceway that is occupied, and the smallest trade size that would have worked.
- An outlet box and a bundle of conductors. The box fill calculator counts them the way the code counts them, including the two allowances every device yoke takes and the single allowance all the grounds take together.
- A transformer feeding a load that has grown. The transformer size calculator applies a growth margin and returns a standard size rather than the exact number you asked for.
- Equipment that is not running at the power you assumed. The power factor calculator shows how many kVA a load really draws, and the kVA calculator then converts that to the current the conductor has to carry.
- A circuit or battery you want to check before you commit to it. The electrical feeder sizing guide walks a whole feeder through all four checks in the order that keeps them from disagreeing with each other.
Five rules that decide most of these answers
Each tool on this site applies the same handful of rules. They are worth knowing because they are the reason two people with the same numbers can get different answers, and they are the reason a figure that looks generous is sometimes not.
- A continuous load is sized at 125 percent. A load expected to run for three hours or more is treated as 1.25 times its rating, for the conductor and for the overcurrent device alike. A 16 A continuous load is therefore designed as 20 A. The margin is not rounding: a conductor held at its rating for hours runs hotter than one carrying the same current briefly.
- The termination usually picks the column, not the wire. The ampacity of a conductor appears in the table once per insulation rating. A 90 degree conductor landed on a 75 degree breaker may only be used at its 75 degree figure, so the lowest-rated component in the circuit sets the ceiling. Most breakers and lugs are rated 75 degree.
- Small conductors have hard ceilings. Under NEC 240.4(D), 14 AWG is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A regardless of what the ampacity table says the conductor can carry. Sizing to the table value on these three sizes gets a circuit that fails on inspection.
- Raceway fill is a percentage of a real area. One conductor may fill 53 percent of the raceway, two may fill 31 percent, and three or more may fill 40 percent. The area comes from Chapter 9 Table 4 for the raceway and Table 5 for the insulation, which is why the answer changes when the insulation changes.
- In a box, the count is not the count of wires. All the equipment grounding conductors together take one allowance. Each device yoke takes two. A cable clamp inside the box takes one more. That is why a box that looks half empty by eye can be overfilled.
Three worked examples
1. One load, two distances
A 240 V single-phase circuit carries a 40 A continuous load over copper, 60 ft one way. The design current is 40 × 1.25 = 50 A, so the conductor has to carry 50 A. From the 75 degree column, 8 AWG at 50 A qualifies and is not one of the small conductors with a ceiling under 240.4(D). Its voltage drop over 60 ft is about 4.69 V, or 1.95 percent, comfortably inside the 3 percent used for a branch circuit.
Now double the distance to 120 ft and change nothing else. The ampacity answer stays 8 AWG because ampacity does not know how long the run is. The drop answer does not stay: 8 AWG over 120 ft gives about 9.38 V, or 3.91 percent, which is outside the 3 percent target. 6 AWG brings it to about 5.90 V, or 2.46 percent, and that is the size you install. Nothing about the load changed; only the distance did.
2. Five conductors into a raceway
Four 8 AWG THHN conductors plus one equipment grounding conductor is five conductors, so the 40 percent limit applies. From Chapter 9 Table 5, one 8 AWG THHN conductor is 0.0366 square inches, so the five of them occupy 0.1830 square inches. A 3/4 inch EMT has 0.533 square inches of internal area from Table 4, which puts the fill at 34.3 percent and passes. That same raceway holds at most five 8 AWG conductors. A 1 inch EMT has 0.864 square inches, drops the fill to 21.2 percent, and holds up to nine.
The trade size you pick changes the answer, which is why a raceway specified before the conductor count was final is often the reason the pull does not fit.
3. A box with room left in it
Take a 4 inch square metal box, 2-1/8 inches deep, 30.3 cubic inches. With 12 AWG as the largest conductor, each allowance is 2.25 cubic inches. Three current-carrying conductors, one grounding conductor and one device yoke count as six allowances: three for the conductors, one for all the grounds together, and two for the yoke. Six allowances is 13.50 cubic inches, so 16.80 cubic inches are still free.
Six current-carrying conductors in the same box count as nine allowances, or 20.25 cubic inches, which still passes. The point of the calculation is not that this box is full; it is that the free space you can see is not the free space the code counts, and the box that looks tightest is often the one with room.
What these calculators do not decide
Each tool here answers one arithmetic question and stops there. Five things sit outside that arithmetic and each of them can change the answer, so none of these numbers is a design on its own.
- Ambient temperature and bundled conductors. The ampacity table assumes 30 degrees C and no more than three current-carrying conductors in a raceway. A run through a 50 degree mechanical room, or eight conductors sharing one conduit, has to be adjusted down from the table value before any of these answers holds.
- Where the circuit has to reach. The voltage drop calculations assume the load is at the far end of the stated distance. A circuit that feeds a second panel feeds everything behind that panel as well.
- What the equipment does on start-up. A motor draws far more than its running current for the first seconds, and its contribution to a feeder is not the same number as the running load.
- Whether the work will be accepted. Every calculation here assumes the circuit is installed to the current code and inspected by someone qualified to judge it. What a given authority will accept is theirs to decide.
What is here
- Design and sizing — voltage drop, conductor sizing, ampacity, transformer sizing and service load.
- Raceway and enclosure — conduit fill and box fill to Chapter 9 and Article 314.
- Power and conversion — kVA, kW, amps, power factor and correction capacitor sizing.
- Electronics — Ohm’s law, power, resistor colour codes and battery runtime.
Instruments for the checks these calculators hand you
Every number on this site comes out of a table, a formula or a code article. Four things turn that number into something you can act on: measuring what is actually there, bending the raceway it has to fit in, identifying it once it is live, and reading the table on site.
- Digital clamp meter — The nameplate on a panel tells you what a circuit was rated for, not what it draws now. A clamp meter reads the running current on each leg without opening the circuit, which is how you find the load that is actually on before you size anything to it.
- Hand conduit bender — The raceway has to be bent to reach the box, and the bend is made on site from the length you chose. A hand bender puts the offset where the drawing needs it and keeps the wall of the EMT from flattening on the way.
- Panel label maker — A service, feeder or branch circuit has to be identified at its disconnecting means so the next person can tell what they are opening. A label printer puts that identification on every circuit instead of on one you remembered.
- Ampacity chart card — The 60, 75 and 90 degree columns of the ampacity table and the small-conductor ceilings are easier to read off a card in a crawl space than off a phone screen, and the card stays in your pocket when the phone has no signal.
As an Amazon Associate I earn from qualifying purchases. The links above are affiliate links — if you buy through one, the price you pay is unchanged and a small commission helps keep these calculators free. Items are listed because the job calls for them, not because of commission rates.
Where these numbers come from
Ampacity values are read from the copper column of NEC Table 310.16, kept separate per temperature rating rather than merged. Conductor areas follow Chapter 9 Table 5 for THHN, raceway areas Table 4 for EMT, and K is 12.9 ohm-circular-mil per foot for copper at 75 degrees. The safety rules the arithmetic sits inside are federal requirements, and the ampere itself is an SI unit with a fixed definition.
- 29 CFR 1910 Subpart S — Electrical (eCFR) — 1910.303 general requirements, 1910.304 wiring design and protection including overcurrent protection and grounding of terminals and devices, 1910.308 special systems including marking of disconnecting means, and 1910.331 to 1910.360 safety-related work practices for qualified persons.
- OSHA — Electrical — the standards that apply to people exposed to electrical hazards, described as protecting employees against electric shock, electrocution, fires and explosions.
- NFPA 70, National Electrical Code — the code the ampacity, overcurrent and fill rules above come from, and the process by which it is revised.
- NIST — SI Units, Electric Current — the ampere, defined from the fixed numerical value of the elementary charge, which is why current is the unit every calculation here starts and ends in.
- Ampacity — the maximum current that can be applied continuously without harming a device or system, as the National Electrical Code defines it.
- Voltage drop — the loss of electric potential along the path of a current, across conductors, contacts and connectors, and the reason it is dissipated as heat.
Everything runs in your browser. Nothing is uploaded, there is no account, and the calculators keep working offline once the page has loaded.